EP 1110-1-18
24 Apr 00
f. Lightning Protection.
(1) FUDS. Lightning protection is not required on FUDS if the following criteria are met:
(a) The magazine is constructed of metal that is 3/16 inch steel or larger in accordance with
National Fire Protection Association (NFPA) 780.
(b) The magazine is grounded in accordance with NFPA.
(c) The magazine is located at least 6.5 feet from the nearest fence.
(2) BRAC and Active Installations. Lightning protection for BRAC or IRP sites will meet
the provisions of DOD 6055.9-STD. Army installations will also meet the provisions of DA
Pamphlet 385-64.
g. Fire Protection. Extinguishers of appropriate size and type will be located in all
14-4